SDI-12 8-channel interface TBSPT8

Application Areas

Producer

Product type

Category

The SDI-12 8-channel interface TBSPT8 PT100/PT1000 from Tekbox is a precision 8-channel PT100/PT1000 interface. Measurement and configuration are controlled via SDI-12 commands. The interface is equipped with 4-wire inputs, matched noise filters, overvoltage and overcurrent protection. To achieve high precision, the TBSPT8-DR is calibrated to an absolute accuracy of ±0.02°C at 0°C using a standard of ±0.005%, ±2 ppm/°C.

Find further information further down the page or call +45 42 42 50 80.

Description

SDI-12 8-channel interface TBSPT8 for environmental monitoring

The SDI-12 8-channel interface TBSPT8 PT100/PT1000 from Tekbox is a precision 8-channel PT100/PT1000 interface. Measurement and configuration are controlled via SDI-12 commands.

The interface is equipped with 4-wire inputs, matched noise filters, overvoltage and overcurrent protection.

To achieve high precision, the TBSPT8-DR is calibrated to an absolute accuracy of ±0.02°C at 0°C using a standard of ±0.005%, ±2 ppm/°C.

The device has a resolution of 0.001°C and a temperature drift of less than ±0.01°C over the temperature range of -40°C to +80°C. Noise is ±0.0015°C when used with PT1000 sensors and ±0.01°C when used with PT100 sensors.

The device can output the measurement results in °Celsius or °Fahrenheit.

The TBSPT8-DR is factory calibrated for absolute accuracy at 0°C and temperature drift compensation. The user can calibrate the absolute accuracy of the device using an extended SDI-12 command. Additionally, it requires 100 Ohm/1000 Ohm resistance standards with an accuracy of at least 0.005%, ±2 ppm/°C.

User calibration of the temperature drift compensation is not required. However, a corresponding extended SDI-12 command is available. However, it requires a thermal chamber to perform the drift calibration process.

  • Precision, 4-wire PT100 / PT1000 interface
  • 8 measuring channels
  • Resolution: 0.001 ° C
  • Noise: ± 0.0015 ° C (PT1000)
  • Absolute accuracy at 0 ° C: ± 0.02 ° C
  • Measuring range: -80 ° C to + 300 ° C
  • Temperature drift: <± 0.01 ° C
  • Configurable measurement units: ° C, ° Fahrenheit
  • Overvoltage and overvoltage protection
  • SDI – 12 standard V1.3
  • Plug and play
  • 6 – 16V supply voltage
  • 115 mm x 90 mm x 57 mm
  • DIN-rail housing
  • Operating temperature range: – 40 ° C … + 85 ° C